TRUE ON LINE UPS TRUE ON LINE UPS
Problem
Possible cause
Remedy
No indication, no warning tone
even though system is
connected to mains power
supply
No input voltage
Input switch has
disconnected
[for 6K(H)/ 10K(H)]
Check building wiring socket outlet
and input cable.
Set the Input switch to ON
LINE LED blinks Phase and neutral
conductor at input
of UPS system are
reversed
Rotate mains power socket by 180
or connect UPS system according to
chapter 5 onnection and operation .
LINE LED blinks and
BATTERY-LED lights up
Input power and/or
frequency are out of
tolerance
Check input power source and
inform dealer if necessary
LINE and BYPASS LED light
up even though the power
supply is available
Inverter not
switched on
Press On-Switch I
INVERTER LED lights up,
and audible alarm sounding
every 1 or 4 seconds
Mains power supply
has failed
Switching to battery mode automatically.
When audible alarm sounding every
second, battery is almost empty.
INVERTER LED lights up,
warning tone at intervals of
every 1 or 4 seconds, mains
power supply available
[for 6K/ 10K]
Input switch
disconnected
Set the Input switch to ON . If the
problem persists, please inform
your dealer.
FAULT LED lights, warning
tone once a second
Overload Remove loads of UPS output.
FAULT-LED lights up,
permanent warning tone
UPS fault Notify dealer!!
Emergency supply period
shorter than nominal value
Batteries not fully
charged / batteries
defect
Charge the batteries for at least
1 - 2 hours and then check
capacity. If the problem still
persists, consult your dealer.
FAULT LED lights, BATTERY-
LED blinks, warning tone once
a second
Charger or
Batteries damaged
Notify dealer!!
FAULT LED lights,Indicator3
and Indicator6 lights,
permanent warning tone
BATSCR short
[for 6K/ 10K]
Notify dealer!!
Please have the following information at hand before calling the After-Sales Service
Department:
1. Model number, serial number
2. Date on which the problem occurred
3. Detailed description of the problem
7. Maintenance
7-1 Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5
years at 25 ambient temperature) has been exceeded, the batteries must be replaced.
In this case please contact your dealer.
7-2 Storage
If the batteries are stored in temperate climatic zones, they should be charged every
three months for 8-10 hours (see Chapter 5 "Connection and Operation"). You should
shorten the charging intervals to two months at locations subject to high temperatures.