7.3 Typical stored energy time (Battery mode)
Typical values at 25°C in minutes:
Model 100% LOAD 50% LOAD
1KVA 5 14
2KVA 9 21
3KVA 5 17.5
7.4 Dimensions and weights
Tower UPS
Model
Dimensions, D*W*H (mm) Net Weight (kg)
1KVA 408*143*207 13
2KVA 460*192*340 32
3KVA 460*192*340 33
Battery Bank for Tower UPS
Model
Dimensions, D*W*H (mm) Net Weight (kg)
BB-36V-14AH
FOR 1K
408*143*207 20
BB-96-14AH
FOR 2K/3K
460*192*340 50
19” Rack-mount UPS
Model
Dimensions, D*W*H (mm) Net Weight (kg)
1KVA 465*19”*2U 16
2KVA 465*19”*2U 33
3KVA 465*19”*2U 33
Battery Bank for 19” Rack-mount UPS
Model
Dimensions, D*W*H (mm) Net Weight (kg)
BB-36V-14AH
FOR 1K
465*19”*2U 38
BB-96V-7AH
FOR 2K/3K
465*19”*2U 43
7.5 Communication Port
The following is the pin assignment and description of DB-9 connector.
Pin# Description I/O
2 TXD Output
3 RXD Input
5 GND Input
9 Wake up Output
- 9 -
4. Connection and Operation
The system may be installed and wired only by qualified electricians in accordance with
applicable safety regulations!
When installing the electrical wiring, please note the nominal amperage of your incoming
feeder.
4.1 Inspection
Inspect the packaging carton and its contents for damage. Please inform the transport
agency immediately should you find signs of damage.
Please keep the packaging in a safe place for future use.
NOTE: Please ensure that the incoming feeder is isolated and secured to prevent it from
being switched back on again.
4.2 Connection
4.2.1 UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket with protection
against electric current, and pay attention to the capacity of the socket: over 10A for
1KVA and over 16A for 3KVA.
4.2.2 UPS Output Connection
Output Socket :IEC/ NEMA 5-15R (pcs)
Model
Tower UPS 19” Rack-mount UPS
Terminal Block
1KVA 4 / 3 2 / 6 Nil
2KVA 2 / 6 4 / 3 Available
3KVA 2 / 6 4 / 3 Available
4.3 Computer Connection
Connect your computer th the outlet sockets of the UPS system following the above
procedure.
Caution!
* Do not connect equipment which would overload the UPS system (e.g.
laser printers).
* Do not connect domestic appliances to the UPS system.
4.4 Battery Charge
Fully charge the batteries of the UPS system by leaving the UPS system connected to the
mains for 1-2 hours. You may use the UPS system directly without charging it but the
stored energy time may be shorter than the nominal value specified.
4.5 Turn On
To turn on the UPS system, press the ON-Switch “I“ on the front panel.
NOTE: The INVERTER-LED lights up after 10 seconds. The BYPASS-LED then goes out
and the ventilation system switches on. The UPS system is now operating correctly.
4.6 Test Function
Test the function of the UPS system by either pressing the On-Switch “I“ or disconnecting
the input of the UPS system from the power supply.