5. Troubleshooting
If the UPS system does not operate correctly, please attempt to solve the problem
using the table below.
Problem Possible cause Remedy
No indication, no
warning tone even
though system is
connected to mains
power supply
No input voltage
Check building wiring socket
outlet and input cable
LINE LED blinks
Phase and neutral
conductor at input of
UPS system are
reversed
Rotate mains power socket by
180° or connect UPS system
according to chapter 5
“Connection and operation”
LINE-LED blinks and
BATTERY-LED lights
up
Input power and/or
frequency are out of
tolerance
Check input power source and
inform dealer if necessary
LINE and BYPASS LED
light up even though
the power supply is
available
Inverter not switched
on
Press On-Switch “I
INVERTER LED lights
up, warning tone at
intervals (every 1 or 4
seconds)
Mains power supply
has failed
Switching to battery mode
automatically. When audible
alarm sounding every 1
second, battery is almost
empty.
FAULT LED lights,
warning tone once a
second
Overload Remove loads of UPS output
FAULT-LED lights up,
permanent warning
tone
UPS fault Notify dealer!!
Emergency supply
period shorter than
nominal value
Batteries are not fully
charged / batteries
defective
Charge the batteries for at least
1-2 hours and then check
capacity. If the problem still
persists, consult your dealer.
Please have the following information at hand before calling the After-Sales Service
Department:
1. Model number, serial number
2. Date on which the problem occurred
3. Detailed description of the problem
- 7 -
6. Maintenance
6.1 Operation
The UPS system contains no user-serviceable parts. If the battery service life (3 - 5
years at 25 °C ambient temperature) has been exceeded, the batteries must be
exchanged. In this case, please contact your dealer.
6.2 Storage
If the batteries are stored in temperate climatic zones, they should be charged
every three months for 1-2 hours (see Chapter "Connection and Operation"). You
should shorten the charging intervals to two months at locations subject to high
temperatures.
7. Technical data
7.1 Engineering specifications
MODEL 1KVA 2KVA 3KVA
INPUT
Phase Single
Frequency 46 Hz ~ 54Hz / 56 Hz ~ 64 Hz
Current (A) 110V / 220V 12A / 7A 20A/10A 30A / 16A
OUTPUT
Power rating 1KVA / 0.7KW 2KVA/1.4KW 3KVA / 2.1KW
Voltage 110 / 115 / 120 or 220 / 230 / 240 * ( ± 2%) VAC
Frequency (50Hz/ 60Hz ) * (± 0.2%) Hz (Battery Mode)
Wave Form Sinusoidal
BATTERIES
Number and Type 3 * 12V / 7Ah 8 * 12V / 7Ah
7.2 Operating Environment
Ambient Temperature 0 to 40
Operating Humidity 20% to 90%, non-condensing
Altitude <1500m
Storage Temperature -15 to 40
- 8 -