10. Technical Data
10.1 Electrical specifications
INPUT
Model No. 1K(S) 1.5K(S) 2K(S) 3K(S)
Phase 1
Frequency (45~55)/(54~66) Hz
Max Current(A)
7.5 10.5 13.5 20
OUTPUT
Model No. 1K(S) 1.5K(S) 2K(S) 3K(S)
Power rating 1kVA/0.9kW
1.5k/1.35kW
2kVA/1.8kW
3kVA/2.7kW
Voltage 208/220/230/240 1 1% VAC
Frequency 50/60 0.2 Hz (Battery mode)
Wave form sinusoidal
BATTERIES
Model No. 1K 1.5K 2K 3K
Number and type
3 12V 7Ah
4 12V 7Ah
4 12V 9Ah
6 12V 9Ah
10.2 Operating Environment
Ambient Temperature 0 C to 40 C
Operating humidity < 95%
Altitude < 1000m
Storage temperature 0 C to 45 C
10.3 Typical backup time (Typical values at 25°C in minutes:)
Model No. 100 % Load 50 % Load
1K 5 15
1.5K 4 12
2K 3 10
3K 3 10