3: Installation and Set-up
3-12 UPS724-01-00 PowerWave 1000 (1-3kVA) User Manual - Dated 26 June 2013
2. Once all the parameters have been selected, click the Write button to send the data to the UPS.
a) Click the Yes button in the Writing?? confirmation dialog.
b) The UPS will beep twice to confirm that it has received the data.
c) Click OK to clear the Transmit OK dialog.
3. In order to apply the changes you must now turn OFF the UPS input supply then turn it back ON again.
3.6.4 Managing the UPS data file
You can open the UPS configuration data file stored on your computer at any time using File>Open from
the menu bar, as described in paragraph 3.6.2. An example data file is shown below. When the file is open
you can select a record by clicking anywhere in the record line – a selected record is highlighted blue.
Adding a new record to the UPS data file
1. As described above, to add the current configuration to the UPS data file, select Record>Add New on
the UPS Setting Tool menu bar.
a) The new record will be added to the bottom of the data file.
Updating an existing UPS data file record
To update an existing data file record with configuration data displayed in the UPS Setting Tool:
1. Open the UPS data file.
2. Select the particular record that you want to update.
3. Click the Unlock button that appears between the Read and Write buttons on the UPS Setting Tool.
4. Ensure that the UPS Setting Tool contains the required update data.
5. Select Record>Update from the UPS Setting Tool menu bar.
a) Click the Yes button in the Update?? confirmation dialog.
b) The UPS data file record will now be updated.
Applying configuration data from an existing record
Use this procedure to set up the UPS using data obtained from an existing data file record.
1. Open the UPS data file.
2. Select the data record that you want to apply to the UPS.
3. Click the Unlock button that appears between the Read and Write buttons on the UPS Setting Tool.
4. The UPS Setting Tool data fields will now be populated with data retrieved from the selected data record.
5. Click the Write button to send the data to the UPS.
a) Click the Yes button in the Writing?? confirmation dialog.
b) The UPS will beep twice to confirm that it has received the data.
c) Click OK to clear the Transmit OK dialog.
6. In order to apply the changes you have made you must now turn OFF the UPS input supply then turn it