4: Operating Procedures
4-4 UPS724-01-00 PowerWave 1000 (1-3kVA) User Manual - Dated 26 June 2013
4.2.2 Enable/disable the audible alarm
Battery test
You can use the following procedure to enable or disable the audible alarm operation. This will not affect the audible
beeps associated with pressing the control buttons, which will remain active even if the audible alarm is turned off.
Note: If the UPS is powered down and disconnected from its input supply, the audible alarm status will revert to
ON
b_on (default) when the UPS is next started.
1. With the UPS on-line, press the FUNCTION button.
a) The LCD will display either
b_on or b_of. This indicates that the
UPS is now in its operator set-up mode and shows the current
operational status of the audible alarm.
b_on = audible alarm enabled – b_of = audible alarm disabled.
2. Press the UP button to select the wanted audible alarm status.
3. Press the FUNCTION button to activate the selected status and return to
the normal LCD Display.
Note: If you do not press the
FUNCTION
button the LCD will revert to its
normal display automatically after approximately 10 seconds and the
selected audible alarm setting will be activated.
You can carry out a periodic battery test using the following procedure. This test effectively places the UPS in its On-
Battery mode for approximately 10 seconds, during which time the control electronics monitors the battery performance.
1. With the UPS turned ON, press the FUNCTION button.
a) The LCD will display b_on (or b_of).
2. Press the DOWN button.
a) The LCD will display tnon.
3. Press the UP button
a) The LCD will momentarily display
trun followed by teSt, which
will remain on the display while the battery test takes place.
4. When the test is completed the LCD will display this “OK” screen if the
battery test was successful, otherwise it will show
fAIL.
Note: If the UPS fails the battery test contact your supplier for technical
assistance.