2: Description
2-2 UPS724-01-00 PowerWave 1000 (1-3kVA) User Manual - Dated 26 June 2013
2.1.2 Advanced design features
The active power factor correction (PFC) control function continuously corrects the UPS input power
factor (PF) to > 0.99, which results in outstanding energy efficiency.
The wide input voltage tolerance, from 120V~288V, allows the UPS to operate normally without
draining the battery unnecessarily during mains under-voltage or overvoltage conditions – which
extends the battery service life.
A DC-start function permits the UPS to be started during a utility power failure if required.
A revolutionary battery management circuit continuously analyses the battery status during discharge
and adjusts the battery cut-off point accordingly – which extends the battery service life.
Selectable bypass input voltage tolerance (low/high sensitivity) to restrict the range of voltages that
can be applied to the load when the UPS operates on bypass.
The selectable voltage ranges are 184~260V (low sensitivity) and 194~260V (high sensitivity).
A selection of output voltages (200/208/220/230/240) is available to match the UPS output to local
supply specifications or specific load voltage requirements.
An overload protection system that automatically switches the UPS to bypass mode in the event of an
overload that exceeds its rated capacity – and automatically switches back to the inverter mode once
the overload condition clears.
Output short-circuit protection which puts the UPS system in stand-by mode and cuts off the output
supply until the short circuit is manually remedied.
2.1.3 PowerWave 1000 Model range
The PowerWave 1000 UPS range compromises 1 kVA, 2 kVA and 3 kVA models, each of which is designed
as a self-contained UPS comprising a rectifier, battery charger, inverter, static switch and battery pack. All the
models in this range are easy to install, and supplied with suitably terminated mains power cables.
The PowerWave 1000 operates as a stand-alone UPS module and can be mechanically configured as a
floor-standing tower unit or installed in a standard 19 inch rack. An accessory pack which contains all the
parts necessary to configure the unit for either type of installation is supplied with the UPS.
An optional external battery cabinet is available to increase the UPS autonomy time. The battery cabinet
design compliments the UPS cabinet and the two cabinets can be mechanically connected together to form a
single unit when installed as a tower system – see chapter 3 (Installation) for mechanical configuration
details.
CAUTION: In spite of their plug-and-play design, it is recommended that the UPS is installed
and configured by a suitably trained engineer.
1 kVA 2 kVA 3 kVA
Maximum output power kVA (kW) 1.0 (0.8) 2.0 (1.6) 3.0 (2.4)
Dimensions (WxHxD) mm 89 x 445 x 405 89 x 445 x 680 89 x 445 x 680
Weight (with standard batteries) kg 19 30 33
Sound level dBA 50 50 50