2: Description
2-4 UPS724-01-00 PowerWave 1000 (1-3kVA) User Manual - Dated 26 June 2013
2.2.2 System operating modes
ON-LINE operation
Figure 2.2 ON-LINE operation
• The battery is being permanently charged by the battery charger.
• The AC/DC converter is processing the utility input supply and turning it into controlled DC.
• The Inverter is converting the AC/DC converter output back into AC suitable for the load.
• The static switch is connecting the inverter output to the UPS output terminals.
ON BATTERY operation
Figure 2.3 ON-BATTERY operation
• The battery is discharging through the DC/DC boost converter which presents the inverter with a
controlled input voltage as the battery discharges.
• The Inverter is converting the DC/DC boost converter output back into AC suitable for the load.
• The static switch is connecting the inverter output to the UPS output terminals.
• The load will continue to receive its regulated power until the battery discharges to its low voltage cut-
out level.
EMI
FILTER
EMI
FILTER
AC/DC (PFC)
CONVERTER
DC/AC
INVERTER
STATIC
SWITCH
BATTERY
CHARGER
DC/DC BOOST
CONVERTER
BATTERY
AC
Input
AC
Output
Bypass Line
Safety
Relay
Input
CB
EMI
FILTER
EMI
FILTER
AC/DC (PFC)
CONVERTER
DC/AC
INVERTER
STATIC
SWITCH
BATTERY
CHARGER
DC/DC BOOST
CONVERTER
BATTERY
AC
Input
AC
Output
Bypass Line
Safety
Relay
Input
CB