UPS724-01-00 PowerWave 1000 (1-3kVA) User Manual - Dated 26 June 2013 4-5
4: Operating Procedures
4.3 Shutdown procedures
4.3.1 Normal shutdown (with mains available)
4.3.2 UPS shutdown when on battery
This procedure describe the shutdown sequence when turning OFF the UPS
when it is operating in its normal ‘On Line’ mode.
Note: Before you shut down the UPS make sure it is safe to disconnect the
critical load power.
1. Press the OFF button for approximately 3~5 seconds, until you hear two
beeps, then release it.
a) The two programmable UPS outlet leds will extinguish to indicate the
removal of UPS output power.
b) The input mains and bypass supply leds will remain lit.
c) The LCD screen will show the UPS status as oFF.
d) On the LCD mimic, the load will be shown disconnected from the
UPS but the battery still connected to the input LINE and on charge.
2. To completely shut down the UPS, disconnect the UPS utility mains
supply.
a) The UPS fans and control panel will remain operative for a few
seconds before the unit completely shuts down.
This procedure describe the shutdown sequence when turning OFF the UPS
when it is operating in its standby, ‘On Battery’, mode. You would typically
use this procedure during a prolonged utility mains failure if you chose to
shutdown the critical load, followed by the UPS, in a controlled manner
before the battery reaches the end of its autonomy time.
1. Turn OFF the UPS by pressing the OFF button for approximately 3~5
seconds, until you hear two beeps, then release it.
a) The two programmable UPS outlet leds will extinguish to indicate the
removal of UPS output power.
b) The LCD screen will show the UPS status as
oFF.
c) On the LCD mimic, the load will be shown disconnected from the
UPS.
2. After a few seconds the UPS will completely shut down and all led and
display indications will extinguish.