2: Description
2-8 UPS724-01-00 PowerWave 1000 (1-3kVA) User Manual - Dated 26 June 2013
Mimic diagram
Figure 2.7 LCD Mimic diagram
Four digit alpha-numeric display
The four digit alpha-numeric display provides a metering facility which can be selected to show the input
voltage/frequency, output voltage/frequency/load together with battery voltage and the internal enclosure
temperature. Details of the meter facilities are provided on page 4-3.
A variety of operating status and fault codes are also shown on the display, as described throughout this
manual.
Load transfer
Load transferred to bypass due to loss of UPS Inverter output.
Bypass defective
Bypass input abnormal, UPS fails to transfer to bypass
Utility supply defective
Utility supply defective at the UPS input terminals.
UPS OFF
This mimic is displayed when the utility power is first applied to the UPS, or if the UPS is
turned OFF. It shows that the battery is being charged from the utility (LINE) but the LOAD
is isolated from the UPS, and is therefore unpowered.
UPS ON
This mimic is displayed during normal UPS operation. It shows the battery being charged
from the utility (LINE) and the LOAD connected to the UPS output – and therefore being
supplied with processed, backed-up power.
ON BATTERY MODE
This mimic is displayed if the utility supply fails. It shows the battery now providing the UPS
and LOAD power. The battery will sustain the UPS output until it is discharged, whereupon
the UPS will shutdown.
LOAD ON BYPASS MODE
This mimic is displayed if the UPS develops a fault (or is overloaded), whereupon the load
is transferred to the bypass line and therefore connected directly to the unprotected utility
supply (LINE). The battery will remain on charge if the UPS charger is healthy.
The load can be manually switched between the UPS and Bypass by simultaneously
pressing the ON and UP buttons for approximately 5 seconds.
LINE UPS LOAD
LCD Mimic diagram
The LCD Mimic indicates the existing power flow through the UPS. The LINE,
UPS, LOAD and BATTERY symbols are permanently shown on screen and their
interconnecting lines appear depending on the UPS mode of operation – see
below.
Note that the arrowheads shown in Figure 2.7 are used in conjunction with the
LCD meter display to identify the source of the meter indication.
LINE UPS LOAD
LINE UPS LOAD
LINE UPS LOAD
LINE UPS LOAD